We take "customer-friendly, quality-oriented, integrative, innovative" as objectives. "Truth and honesty" is our management ideal for Abb Dsax 110 57120001-Pc , ABB 07AC91 GJR5252300R0101 , Abb Di810 3bse008508r1 , Our mission is to allow you to create long-lasting relationships together with your consumers via the ability of marketing merchandise.
Industrial Automation triple-module redundancy (TMR) architecture Company – ABB BC810K02 3BSE031155R1 3BSE038692R1 CEX-bus Interconnection Unit – RuiMingSheng Detail:

Description

Manufacture ABB
Model BC810K02
Ordering information 3BSE031155R1 3BSE038692R1
Catalog 800xA
Description BC810K02 CEX-bus Interconnection Unit
Origin Sweden (SE)
HS Code 85389091
Dimension 16cm*16cm*12cm
Weight 0.8kg

Details

  • Catalog Description:
    BC810K02 CEX-bus Interconnection Unit
  • Long Description:
    Including:
    - 2 pcs BC810, Interconnection Unit
    - 2 pcs TP857, Baseplate
    - TK851, Interconnection Cable
    - 2 pcs TB850, CEX-Bus Terminator
    The BC810 unit consists of two basic parts: baseplate (TP857) and power supply/logic board. The baseplate is where the connectors to CEX-Bus and the external power reside. It is grounded to the DIN-rail through metal parts of the housing. The board also carries the external power voting diode and fuse. The power supply and logic board contains the +3.3 V converter, logic, drivers for CEX-Bus interconnection and the connector for interconnection cable.

    BC810 can be used with PM861A, PM862, PM864A, PM865, PM866, PM866A and PM867.

    In a fully redundant system with two interlinked BC810 and primary/backup CPU pair, the BC810 support online replacement of the CPU baseplate without disturbing the CEX traffic. If the BC810 has to be replaced, all traffic to the connected CEX segment are stopped.

    The CEX-Bus is used for extending the on-board communication ports with communication interface units. It is also possible to use redundant communication interfaces on the CEX-Bus. The CEX-Bus Interconnection unit BC810 is used to increase the availability on the CEX-Bus by dividing it into separate segments. This improves the availability in systems with redundant communication interfaces.

    Features and benefits

    • Supports redundant communication interface units.
    • Supports on-line replacement of the CPU.
    • External power supply.
    • Supports hot swap


Datasheet link


Product detail pictures:

Industrial Automation triple-module redundancy (TMR) architecture Company –  ABB BC810K02 3BSE031155R1 3BSE038692R1 CEX-bus Interconnection Unit – RuiMingSheng detail pictures


Related Product Guide:

Together with the "Client-Oriented" enterprise philosophy, a arduous good quality control technique, sophisticated producing equipment and a sturdy R&D staff, we generally offer superior quality merchandise, superb solutions and aggressive rates for Industrial Automation triple-module redundancy (TMR) architecture Company – ABB BC810K02 3BSE031155R1 3BSE038692R1 CEX-bus Interconnection Unit – RuiMingSheng , The product will supply to all over the world, such as: Honduras, United Arab emirates, Ethiopia, Excellent quality, competitive price, punctual delivery and dependable service can be guaranteed. For further inquires please do not hesitate to contact us. Thank you - Your support continuously inspires us.
  • Sales manager is very enthusiastic and professional, gave us a great concessions and product quality is very good,thank you very much!
    5 Stars By Lena from Tunisia - 2018.02.12 14:52
    The factory workers have rich industry knowledge and operational experience, we learned a lot in working with them,we are extremely grateful that we can encount a good company has excellent wokers.
    5 Stars By Catherine from Slovak Republic - 2017.09.30 16:36

    Send your message to us: