Honeywell XFL823A Distributed I/O Module
Description
| Manufacture | Honeywell |
| Model | XFL823A |
| Ordering information | XFL823A |
| Catalog | TDC2000 |
| Description | Honeywell XFL823A Distributed I/O Module |
| Origin | USA |
| HS Code | 3595861133822 |
| Dimension | 3.2cm*10.7cm*13cm |
| Weight | 0.3kg |
Details
Manual Overrides as per EN ISO 16484-2:2004 The manual override switches and potentiometers of the output modules (…R822A, …R824A,) support direct operation as per EN ISO 16484-2:2004, section 5.4.3 "Local Priority Override/Indicating Units." Specifically, the positions of the manual override switches and potentiometers directly control the outputs – independently of the Excel Web Controller and HMI. When a manual override switch or potentiometer is not in its default position ("auto"), the corresponding output LED will blink continuously, and the output module will send a feedback signal with the status "manual override" and the given override position to the Excel Web Controller (which will then also store this information in its alarm memory). Note: When updating the firmware of output modules, their outputs are turned OFF – regardless of the position of their manual override switches and/or potentiometers.