Details
Replacing an output module All output modules can be replaced with the power switched on. Depending on the output signal function and the system IO configuration, process operation may be affected. When removing an output module, first disconnect the flat cable from the horizontal IO bus (IOBUS-HBS or IOBUS-HBR), loosen the screws, then carefully pull the module from the chassis. When placing an output module, carefully push the module into the chassis until it is flush with the chassis, fasten the screws, then connect the flat cable to the horizontal IO bus (IOBUS-HBS or IOBUS-HBR). Output load, current limiting and supply voltage The digital outputs with transistor outputs are provided with an electronic current-limiting circuit. If the output is overloaded or shorted, it goes in current limit for a brief period of time (several milliseconds), supplying at least the specified maximum output current. If the overload or short-circuit persists, the output switches off. Safety-related outputs will then generate a Safety Manager system fault, and remain de-energized until a fault reset is given. Non-safety-related outputs switch on again after a delay of several hundreds of milliseconds (see Figure 203 on page 348). A system fault is only generated if the output is a safe type.