Honeywell CC-PDOB01 51405043-175 Digital Output 24V Module
Description
Manufacture | Honeywell |
Model | CC-PDOB01 |
Ordering information | 51405043-175 |
Catalog | Experion® PKS C300 |
Description | Honeywell CC-PDOB01 51405043-175 Digital Output 24V Module |
Origin | USA |
HS Code | 3595861133822 |
Dimension | 3.2cm*10.7cm*13cm |
Weight | 0.3kg |
Details
5.11.2 Using DI 24V module (Cx - TDIL51, Cx - TDIL61) channels to report system alarms You must include digital input channels in the control strategy to generate and report alarms based on their PVs. A typical strategy consists of a Control Module that contains the DI channel blocks where each PV (output) is connected to a PVFL input of a FLAGARRAY block configured for alarming. The normal condition of the alarm input is ON. Refer to the Control Building Guide for the following topics • Creating and saving a control module • Creating an instance of a basic function block • Configuring alarms Prerequisites • You have installed and configured Series C 24V digital input I/O modules and associated IOTAs. • You have alarm cables 51202343-001 (12-foot long) to connect power supply alarm contacts to 24V dc digital inputs on the IOM. To connect the Power System alarm cable for RAM Charger Assembly 51199932-200 1 Plug the connection end of the alarm cable into the alarm connection on top of the power supply. 2 Connect the twisted pair wires to the terminal block 1 on the DI 24V IOTA in the following configuration. The associated alarm pins are also displayed.