Honeywell CC-PAON01 51410070-176 Analog Output (AO) Module
Description
Manufacture | Honeywell |
Model | CC-PAON01 |
Ordering information | 51410070-176 |
Catalog | Experion® PKS C300 |
Description | Honeywell CC-PAON01 51410070-176 Analog Output (AO) Module |
Origin | USA |
HS Code | 3595861133822 |
Dimension | 3.2cm*10.7cm*13cm |
Weight | 0.3kg |
Details
Function
The LLMUX IOP module supports up to 64 channels of temperature inputs. Low level inputs use the Honeywell PMIO
LLMUX FTA. Each FTA supports 16 channels. Two types of LLMUX FTA are supported. One provides 16 RTD inputs.
The other provides 16 TC or MV inputs. Any combination of FTAs may be used to provide the mix of TC, mV or RTD
points required.
Notable Features
•
TC and RTD operation
•
Remote cold junction capability
•
1 Second PV scanning with OTD protection
•
Configurable OTD protection (See below)
•
Temperature points can be added in 16 point
increments
Temperature Support
The Temperature Input LLMUX supports the existing solid state PMIO LLMUX FTA. The PMIO LLMUX FTA supports
RTD and Thermocouple (TC) inputs. The Temperature variable is collected from all points at a 1 second rate. The 1
second update includes a configurable check for Open Thermocouple Detection (OTD) (see below) before propagation
of the temperature variable. All TC inputs are compensated using a Cold Junction Compensation (CJT) device.
Sampling and Open Sensor Detect
The Temperature multiplexer supports RTD and Thermocouples with Open Sensor Detect before PV delivered if so
configured. With the OTD configuration active, the PV is sampled and held while an OTD cycle is performed within the
same measurement window. If the OTD is negative, the PV is propagated up through the system. If the OTD is positive,
the PV is set to NAN and the input channel soft failure is set. In this way, no inappropriate control action occurs for PV
values that are invalid due to an open thermocouple. PV sampling/reporting incurs no added delays from OTD
processing.