GE IS220PDIAH1B Discrete Input Module
Description
| Manufacture | GE |
| Model | IS220PDIAH1B |
| Ordering information | IS220PDIAH1B |
| Catalog | Mark Vie |
| Description | GE IS220PDIAH1B Discrete Input Module |
| Origin | USA |
| HS Code | 3595861133822 |
| Dimension | 3.2cm*10.7cm*13cm |
| Weight | 0.3kg |
Details
3.6
PDIA and YDIA Discrete Input Modules
The following I/O pack and terminal board combinations are approved for use in hazardous locations:
•
Mark VIe Discrete I/O pack IS220PDIAH1A
with terminal boards (accessories) IS200STCIH1A, IS200STCIH2A, IS200STCIH8A, IS200TBCIH2C, or
IS200TBCIH4C
•
Mark VIe Discrete I/O pack IS220PDIAH1B
with terminal boards (accessories) IS200STCIH1A, IS200STCIH2A, IS200STCIH8A, IS200TBCIH2C,
IS400TBCIH2C, IS200TBCIH4C, IS400STCIH1A, IS400STCIH2A, or IS400STCIH8A
•
Coated Mark VIe Discrete I/O pack IS221PDIAH1B
with coated terminal boards (accessories) IS201STCIH1A, IS201STCIH2A, IS201STCIH8A, IS201TBCIH2C, or
IS201TBCIH4C
•
Mark VIeS Safety Discrete I/O pack IS220YDIAS1A
with terminal boards (accessories) IS200STCIS1A, IS200STCIS2A, IS400STCIS1A, IS400STCIS2A,
IS200TBCIS2C, or IS400TBCIS2C
•
Mark VIeS Safety Discrete I/O pack ISx2yYDIAS1B (where x = 2 or 4 and y = 0 or 1)
with terminal boards (accessories) ISx0ySTCIS1A, ISx0ySTCIS2A, IS40ySTCIS4A, ISx0yTBCIS2C, or
IS40yTBCIS3C
4.1
Overview
Control power for Mark VIe equipment is distributed from the power supplies to the controllers, Ethernet switches, and I/O
modules through a system of wire harnesses (refer to the tables in the following sections), and power distribution boards
(JPDx).
4.1.1
TMR Control Power using JPDS
A power distribution system using the JPDS power distribution board supports up to three independent control power supply
buses: R, S, and T. Following are specific instructions for these connections:
•
Up to three 24 or 28 V dc, 20 A control power supplies (R, S, T) may be connected to the JPDS board using wire harness
type A. The power supplies are connected to the mains supply.
•
An optional PPDA module is used with the JPDS to monitor the health of the power distribution system. It is connected
directly to I/O connector JA1, and to power supply connector P4 using wire harness type E.
•
The JPDS board supplies R, S, and T power from connectors JAR, JAS, and JAT to controllers using wire harness type B
or Ethernet switches using wire harness type C. Connectors JCR, JCS, and JCT are not used because these outputs are not
current limited.
•
The JPDS board may feed up to six JPDH boards using wire harness type D.
•
The JPDH board fans out control power for up to eight R, S, and T (each) modules using wire harness type E. The R, S,
and T control power buses can be extended to another JPDH from connector J1X using wire harness type D. Connectors
JRS, JSS, and JTS are not used because these outputs are not current limited.
•
The JPDE board can be used to provide redundantly sourced I/O wetting power via outputs JS1-3 and JFA-C. The I/O
wetting power can be further fused and distributed to I/O terminal boards using the JPDD I/O wetting branch power
distribution. Refer to the example diagram and cable table.