Fast and good quotations, informed advisers to help you choose the correct product that suits all your needs, a short production time, responsible quality control and different services for paying and shipping affairs for CI840 3BSE022457R1 , ABB TU836V1 3BSE013237R1 , Abb 07kr91 Gjr5250000r0101 , Created products with brand value. We attend seriously to produce and behave with integrity, and by the favor of customers at home and abroad in the xxx industry.
Best 8516-039 Company - Woodward ART-21819/AIO31 MRU311DM PCM128-HD accessories – RuiMingSheng Detail:

Description

Manufacture Woodward
Model ART-21819/AIO31 MRU311DM PCM128-HD
Ordering information ART-21819/AIO31 MRU311DM PCM128-HD
Catalog MicroNet Digital Control
Description Woodward ART-21819/AIO31 MRU311DM PCM128-HD accessories
Origin United States (US)
HS Code 85389091
Dimension 16cm*16cm*12cm
Weight 0.8kg

Details

A Smart I/O module has its own on-board microcontrollers. The modules described in this chapter are Smart I/O modules. During initialization of a smart module, the module’s microcontroller turns the
LED off after power-on self-tests have passed and the CPU has initialized the module. The LED is illuminated to indicate an I/O fault.

The CPU also tells this module in which rate group each channel is to run, as well as any special information (such as the type of thermocouple in the case of a thermocouple module). At run time, the CPU then periodically broadcasts a “key” to all I/O cards, telling them which rate groups are to be updated at that time.

Through this initialization/key broadcast system, each I/O module handles its own rate-group scheduling with minimal CPU intervention. These smart I/O modules also have on-card on-line fault detection and automatic calibration/compensation. Each input channel has its own precision voltage
reference. Once per minute, while not reading inputs, the on-board microcontroller reads this reference. The microcontroller then uses this data read from the voltage reference for both fault detection and automatic temperature compensation/calibration.

Limits have been set for the expected readings when the on-board microcontroller reads each voltage reference. If the reading obtained is outside these limits, the system determines that the input channel, A/D converter, or the channel’s precision-voltage reference is not functioning properly. If this happens,
the microcontroller flags that channel as having a fault condition. The CPU will then take whatever action the application engineer has provided for in the application program.

A smart output module monitors the output voltage or current of each channel and alerts the system if a fault is detected. Each I/O module has a fuse on it. This fuse is visible and can be changed through a cutout in the plastic cover of the module. If the fuse is blown, replace it with a fuse of the same type and size.

Figure 10-3 is a block diagram of the two-channel actuator controller module. Each channel controls an integrating or proportional, hydromechanical or pneumatic actuator. Each actuator may have up to two position feedback devices. There are several versions available, and the module part number indicates the module’s maximum output current capability. A MicroNet lowdensity discrete (gray) cable must be used with this module. Do not use an analog (black) cable.

This Actuator Driver module receives digital information from the CPU and generates four proportional actuator-driver signals. These signals are proportional and their maximum range is 0 to 25 mAdc or 0 to 200 mAdc.

Figure 10-5 is a block diagram of the four-channel Actuator Driver module. The system writes output values to dual-port memory through the VME-bus interface. The microcontroller scales the values using calibration constants stored in EEPROM, and schedules outputs to occur at the proper time. The microcontroller monitors the output voltage and current of each channel and alerts the system of any channel and load faults. The system can individually disable the current drivers. If a fault is detected which prevents the module from operating, by either the microcontroller or the system, the FAULT LED will illuminate.


Datasheet link


Product detail pictures:

Best 8516-039 Company - Woodward ART-21819/AIO31 MRU311DM PCM128-HD accessories – RuiMingSheng detail pictures


Related Product Guide:

Our primary intention should be to offer our clientele a serious and responsible enterprise relationship, delivering personalized attention to all of them for Best 8516-039 Company - Woodward ART-21819/AIO31 MRU311DM PCM128-HD accessories – RuiMingSheng , The product will supply to all over the world, such as: Anguilla, Stuttgart, Sri Lanka, To keep the leading position in our industry, we never stop challenging the limitation in all aspects to create the ideal products. In his way, We can enrich our life style and promote a better living environment for the global community.
  • The after-sale warranty service is timely and thoughtful, encounter problems can be resolved very quickly, we feel reliable and secure.
    5 Stars By Brook from Myanmar - 2018.12.11 11:26
    The factory has advanced equipment, experienced staffs and good management level, so product quality had assurance, this cooperation is very relaxed and happy!
    5 Stars By Amelia from Finland - 2018.06.09 12:42

    Send your message to us: